Installation Characteristics Of Gate Valves

Aug 08, 2026 Leave a message

1) The installation location, height, and inlet/outlet orientation must comply with design requirements, and connections must be secure and tight.
2) For manual valves installed on insulated piping, the handles must not point downwards.
3) Valves must undergo a visual inspection prior to installation, and their nameplates must comply with the current national standard GB 12220, *General Purpose Valves-Marking*. Valves with a working pressure exceeding 1.0 MPa or those serving as shut-off valves on main pipelines must undergo strength and tightness tests before installation and may only be used if they pass these tests. For the strength test, the test pressure shall be 1.5 times the nominal pressure and maintained for at least 5 minutes; the valve body and packing must show no signs of leakage to be considered acceptable. For the tightness test, the test pressure shall be 1.1 times the nominal pressure; the test duration must comply with the requirements of standard GB 50243, and the valve disc sealing surface must show no signs of leakage to be considered acceptable.
4) Handwheels, handles, and actuating mechanisms must not be used for lifting purposes, and impacts must be strictly avoided.
5) Gate valves equipped with actuating mechanisms must be installed in accordance with the manufacturer's instructions.